1-23
Section 1 Specications
Address Name Description Attribute
%MX1.61480.0
Interrupt input event ag for
rising edge 0
This ag is a special event address that is used for the event
address to set conditions for an event task and not set to ON in
practice. When a rising edge of the signal of the input terminals
X0 to X15 in the main unit is detected, the set event task
operates.
–
| |
%MX1.61480.15
Interrupt input event ag for
rising edge 15
%MX1.61481.0
|
%MX1.61482.15
Not used
%MX1.61483.0
Interrupt input event ag for
falling edge 0
This ag is a special event address that is used for the event
address to set conditions for an event task and not set to ON in
practice. When a falling edge of the signal of the input terminals
X0 to X15 in the main unit is detected, the set event task
operates.
–
| |
%MX1.61483.15
Interrupt input event ag for
falling edge 15
%MX1.61484.0
|
%MX1.61485.15
Not used
%MX1.61486.0
Interrupt input event ag for
rising and falling edges 0
This ag is a special event address that is used for the event
address to set conditions for an event task and not set to ON in
practice. When a rising or falling edge of the signal of the input
terminals X0 to X15 in the main unit is detected, the set event
task operates.
–
| |
%MX1.61486.15
Interrupt input event ag for
rising and falling edges 15
%MX1.61487.0
|
%MX1.61488.15
Not used
%MX1.61489.0
High-speed counter match ag
CH0
This ag is a special event address that is used for the event
address to set conditions for an event task and not set to ON
in practice. When the current value coincides with the set high-
speed counter value, the set event task operates.
–
| |
%MX1.61489.7
High-speed counter match ag
CH7
%MX1.61489.8
|
%MX1.61491.15
Not used
(4) Memories related to interrupt %MW1.61480 to %MW1.61498
These are special relays for the external interrupt input function of the main unit.
1) Interrupt event ag %MW1.61480 to %MW1.61491
%MX1.61476.0 Pulse catch falling edge 0
ON for one scan period during the next scan when a falling edge
pulse that is inputted to the input terminals X0 to X35 of the main
unit is detected.
R
| |
%MX1.61476.15 Pulse catch falling edge 15
%MX1.61477.0 Pulse catch falling edge 16
| |
%MX1.61477.15 Pulse catch falling edge 31
%MX1.61478.0 Pulse catch falling edge 32
| |
%MX1.61478.3 Pulse catch falling edge 35
%MX1.61478.4
|
%MX1.61479.15
Not used