1-15
Section 1 Specications
(9) User fatal fault %MW10.14 to %MW10.16
(10) User nonfatal fault %MW10.18 to %MW10.20
Address Name Description
%MX10.14.0 User fatal fault factor 0
A fatal error occurs and the main unit stops when any of these bits is set to
ON by an application program.
| |
%MX10.14.15 User fatal fault factor 15
%MX10.15.0 User fatal fault factor 16
| |
%MX10.15.15 User fatal fault factor 31
%MX10.16.0 User fatal fault factor 32
| |
%MX10.16.15 User fatal fault factor 47
Address Name Description
%MX10.18.0 User nonfatal fault factor 0
A nonfatal error occurs when any of these bits is set to ON by an application
program. The main unit continues operation.
Set to OFF the bit that has been set to ON by the application program to
restore the main unit from a nonfatal fault condition.
| |
%MX10.18.15 User nonfatal fault factor 15
%MX10.19.0 User nonfatal fault factor 16
| |
%MX10.19.15 User nonfatal fault factor 31
%MX10.20.0 User nonfatal fault factor 32
| |
%MX10.20.15 User nonfatal fault factor 47