1-20
Section 1 Specications
(16) Conguration/conguration fault information %WM10.52 to %WM10.83 (Read only)
This area indicates the status of the expansion units/boards.
Address Name Description
%MX10.52.0 Main unit conguration ON when the main unit is in a normal or a nonfatal fault condition.
%MX10.52.1 Expansion right side unit 1 conguration
When the main unit is powered on, the bit corresponding to the
connected expansion right side unit (including a healthy unit) is set
ON.
If an expansion right side unit is dropped while the main unit is
running, only the conguration bit of the healthy unit is set OFF.
The other conguration bits reMain ON.
* “Expansion right side unit 7 conguration” is assigned only to a
healthy unit when six expansion units (max.) are connected.
%MX10.52.2 Expansion right side unit 2 conguration
%MX10.52.3 Expansion right side unit 3 conguration
%MX10.52.4 Expansion right side unit 4 conguration
%MX10.52.5 Expansion right side unit 5 conguration
%MX10.52.6 Expansion right side unit 6 conguration
%MX10.52.7 Expansion right side unit 7 conguration
%MX10.52.8
|
%MX10.58.3
Not used
%MX10.58.4 Front board conguration ON when the front board is in a normal or nonfatal fault condition.
%MX10.58.5
|
%MX10.64.7
Not used
%MX10.64.8 Expansion left side unit conguration
ON when the expansion left side unit is in a normal or nonfatal fault
condition.
%MX10.64.9
|
%MX10.67.15
Not used
%MX10.68.0 Main unit error ON when the main unit is in a nonfatal or fatal fault condition.
%MX10.68.1 Expansion right side unit 1 error
When a healthy unit is mounted and an expansion right side unit is
dropped, only the error bit corresponding to the healthy unit is set
ON. The other error bits of expansion right side units reMain OFF.
* “Expansion right side unit 7 error” is assigned only to a healthy
unit when six expansion units (max.) are connected.
%MX10.68.2 Expansion right side unit 2 error
%MX10.68.3 Expansion right side unit 3 error
%MX10.68.4 Expansion right side unit 4 error
%MX10.68.5 Expansion right side unit 5 error
%MX10.68.6 Expansion right side unit 6 error
%MX10.68.7 Expansion right side unit 7 error
%MX10.68.8
|
%MX10.74.3
Not used
%MX10.74.4 Front board error
ON when the front board is in a nonfatal or fatal fault condition.
(Note 1)
%MX10.74.5
|
%MX10.80.7
%MX10.80.8 Expansion left side unit error
ON when the expansion left side unit is in a nonfatal or fatal fault
condition. (Note 1)
%MX10.80.9
|
%MX10.83.15
Not used
Notes:
1) A dropout of communication boards/units is not detected.
However, during the CPU link communication, a nonfatal fault occurs if a link station is dropped.