1-13
Section 1 Specications
(4) Resource fatal fault factor %MW10.2 (Read only)
This area indicates the factors of fatal faults. If a fatal fault occurs, the resource (main unit) stops operation.
(5) Resource nonfatal fault factor %MW10.4 (Read only)
This area indicates the factors of nonfatal faults. Even if a nonfatal fault occurs, the resource (main unit) continues operation.
Address Name Description
%MX10.2.0 CPU error ON when a fatal fault occurs in the main unit.
%MX10.2.1 Not used
%MX10.2.2 Memory error ON when an error occurs in the memory in the main unit.
%MX10.2.3 Not used
%MX10.2.4 Application error ON when an error is found in an application program or system denition.
%MX10.2.5 I/O error
ON when communication between the main unit and a healthy unit is
interrupted. I/O errors are not detected if no healthy unit is mounted.
%MX10.2.6
|
%MX10.2.12
Not used
%MX10.2.13 Other hardware error ON when an error occurs in hardware other than the CPU, memory and I/O.
%MX10.2.14 Not used
%MX10.2.15 User fatal fault
ON when one of the user fatal fault ags (%MX10.14.0 to %MX10.166.15) is
turned ON by an application program.
Address Name Description
%MX10.6.0 Arithmetic processor error Hardware error in the arithmetic LSI in the main unit
%MX10.6.1
|
%MX10.6.15
Not used
Address Name Description
%MX10.4.0
%MX10.4.1
Not used
%MX10.4.2 Memory error ON when an error occurs in the memory in the main unit.
%MX10.4.3 Not used
%MX10.4.4 Application error ON when an error is found in an application program or system denition.
%MX10.4.5
|
%MX10.4.13
Not used
%MX10.4.14 Battery error
ON when voltage of the data backup battery drops or when the battery
connection switch is OFF.
%MX10.4.15 User nonfatal fault
ON when one of the user nonfatal fault ags (%MX10.18.0 to %MX10.20.15)
is turned ON by a user program.
(6) CPU error factor %MW10.6 (Read only)