Installing/Removing the Server into/from the Rack Hardware Installation
4.3.1 Requirements of the Rack
The rack systems of the Fujitsu Siemens Computers (PRIMECENTER Rack,
DataCenter Rack) support fully the installation of the PRIMERGY RX100 S3
server system. The installation into the at present usual rack systems of
different foreign manufacturers (3rd-Party Rack) is supported to large part.
To accommodate the ventilation concept and ensure proper ventilation of the
components in the rack, any unused areas must be closed using dummy covers.
The power is supplied via the socket strips available in the rack.
The main features of the rack systems of the Fujitsu Siemens Computers are:
PRIMECENTER Rack
Frontally bolted telescopic rails (in the rear left area a support bracket is
used).
The rails are provided with a linear alignment possibility to ensure also an
adjustment to different rack depths.
DataCenter Rack
Frontally or laterally bolted telescopic rails (in the rear left area a support
bracket is used).
The rails are provided with a linear alignment possibility to ensure also an
adjustment to different rack depths.

Table of Contents

Other manuals for Fujitsu Primergy RX100 S3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Primergy RX100 S3 and is the answer not in the manual?

Fujitsu Primergy RX100 S3 Specifications

General IconGeneral
BrandFujitsu
ModelPrimergy RX100 S3
CategoryServer
LanguageEnglish

Related product manuals