INSTALLATION - 2
2.8 STEAM SAFETY VALVE
Safetyvalvesarefactoryttedandpre-set,theyMUSTNOTbeadjusted.Thedischargeoutlet
should be piped to a safe discharge point and the piping so arranged that any condensate
trapped in the pipework will drain away from the valve.
Note: Safety Valve Outlet connections should be piped two sizes larger than the inlet connection size, this will
ensure there are no accumulation issues.
a) The lift pressure is indicated on the safety valve (do not adjust).
b) Thesafetyvalvettedtotheboilerisdesignedtopreventtheboilerexceedingitsdesign
pressure.
c) Any system connected to the boiler not capable of accepting boiler pressure must be protected
by a separate safety valve set to the required pressure.
WARNING
Factory tted safety valves are pre-set to protect the boiler only and must not be used to protect any
other items not capable of accepting boiler pressure.
Figure. 7 - Safety Valve