EasyManua.ls Logo

FULTON RBC1250 - Annually in Addition

FULTON RBC1250
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RB-RBC-IOMM-2015-1
Fulton Ltd
Page 45
MAINTENANCE - 4
It is a requirement of the Factories Act and Pressure Systems Regulations (UK only) that the
boilerisinternallyinspectedandre-certiedatnotmorethan14monthintervals.
It is normal practice to carry out an annual service during which your insurance surveyor would
attend to carry out the statutory inspection. The scope of a full insurance strip-down is such that
it should only be attempted by persons competent to do so who have had the necessary training,
and have the required test equipment. Fulton Ltd can offer this service if required.
Theengineeringsurveyormayrequiretheremovaloftheceramicbreinsulationaroundthe
periphery of the front tube plate to facilitate inspection of the shell to tube plate weld.
ThestandardFultonservicekitincludesreplacementceramicbrematerialwhichmustbeglued
inplacewiththeadhesivesupplied.Itisvitalthematerialisttedensuringtheendsofthebre
face into the centre of the boiler.
Forburnermaintenance,refertotheburnermanufacturer’sInstallationandMaintenance
instructions.
4.11.5 ANNUALLY IN ADDITION

Table of Contents

Related product manuals