GEK-113032A W650 Wind Generator Protection System 7-15
7 IEC 61850 PROTOCOL 7.2 IEC 61850 PROFILE FOR W650
7
NDPTOC: 3 NEUTRAL TIME OVERCURRENT.
GNDPTOC: 3 GROUND TIME OVERCURRENT AND 3 SENS GROUND TIME OVERCURRENT.
PTOC CLASS
Attribute
Name
Attr.
Type
Explanation M/O Notes
PTOC Time overcurrent
DATA
Common Logical Node Information
Mod geModINC Mode M
Beh geINS Behaviour M
Health geINS Health M
NamPlt geLPL Name plate M
Status Information
Str geNeutACD Start M TOC PKP
Op geNeutACT Operate M TOC OP
Blk geNeutACT Block P TOC BLK
Settings
TmACrv geCURVE Operating curve type M Curve
StrVal geFloatASG Start value O Pickup Level (0,05 - 160)
TmMult geFloatASG Time dial multiplier O TD Multiplier (0 – 900)
RsMod geING_2 Reset Mode P Reset (instantaneous, lineal)
PTOCEna geSPG Function TOC enable P Function
PTOC CLASS
Attribute
Name
Attr.
Type
Explanation M/O Notes
PTOC Time overcurrent
DATA
Common Logical Node Information
Mod geModINC Mode M
Beh geINS Behaviour M
Health geINS Health M
NamPlt geLPL Name plate M
Status Information
Str geNeutACD Start M TOC PKP
Op geNeutACT Operate M TOC OP
Blk geNeutACT Block P TOC BLK
Settings
TmACrv geCURVE Operating curve type M Curve
StrVal geFloatASG Start value O Pickup Level (0,05 – 160)
TmMult geFloatASG Time dial multiplier O TD Multiplier (0 – 900)
RsMod geING_2 Reset Mode P Reset (instantaneous, lineal)
InMagTyp geING_1 Input Type P Input (Phasor, RMS)
PTOCEna geSPG Function TOC enable P Function