GEK-113032A W650 Wind Generator Protection System 7-17
7 IEC 61850 PROTOCOL 7.2 IEC 61850 PROFILE FOR W650
7
AUXPTOV: 3 AUXILIARY OVERVOLTAGE.
PTOV CLASS
Attribute
Name
Attr.
Type
Explanation M/O Notes
PTOV Overvoltage
DATA
Common Logical Node Information
Mod geModINC Mode M
Beh geINS Behaviour M
Health geINS Health M
NamPlt geLPL Name plate M
Status Information
Str geGeneralACD Start M TOV PKP
Op geGeneralACT Operate O TOV OP
Blk geGeneralACT Block P TOV BLK
Settings
StrVal geIntASG Start Value O Pickup Level (3 – 500)
OpDlTmms geFloatASG Operate Delay Time O Trip Delay ( 0 – 900 )
RsDlTmms GeFloatASG Reset Delay Time O Reset Delay ( 0 – 900 )
PTOVEna geSPG Function TOV enable P Function