P44x/EN ST/Hb
P442, P444 (ST) 4-
2.12 Undercurrent protection (“I< protection” menu)
This menu contains undercurrent protection functions.
2.12.1 Undercurrent protection
The undercurrent protection included within the P442 and P444 relays consists of two
independent stages.
Two stages are included to provide both alarm and trip stages, where required. Alternatively,
different time settings may be required depending on the severity of the current dip.
Menu text Default setting
Setting range
Step size
Min Max
GROUP 1 – I< PROTECTION
I< mode 00 00 11 1
The protection is activated with:
– first digit = 1 activates I<1 status,
– second digit = 1 activates I<2 status.
I<1 Status Disabled Disabled / Enabled
Activates or deactivates the first stage undercurrent status
. The two following submenus are
visible when I<1 status is enabled.
I<1 Current Set 0.05 0.08*I1 4*I1 0.01*I1
Pick-up setting for first stage undercurrent element.
I<1 time Delay 1 0 100 0.01
Setting for the first stage undercurrent time-delay.
I<2 Status Disabled Disabled / Enabled
Activates or deactivates the second stage undercurrent status
. The two following submenus
are visible when I<2 status is enabled.
I<2 Current Set 0.1 0.08*I1 4*I1 0.01*I1
Pick-up setting for second stage undercurrent element.
I<2 Time Delay 2 0 100 0.01
Setting for the first stage undercurrent time-delay.
2.13 Voltage protection (“Volt protection” menu)
This protection menu contains undervoltage and overvoltage protection.
2.13.1 Undervoltage protection
Menu text Default setting
Setting range
Step size
Min Max
GROUP 1 – VOLT Protection
V< & V> MODE 00000000 00000000 11111111 1
Activates individually undervoltage or overvoltage threshold, according to the following
table:
V< & V> mode=
1 1 1 1 1 1 1 1
activates: V<1
function
V<2
Status
V<3
Status
V<4
Status
V>1
function
V>2
Status
V>3
Status
V>4