EasyManua.ls Logo

GE P444

GE P444
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P
44x/EN AP/Hb6
Application Notes
(AP) 5
-40 MiCOM P40 Agile
P442, P444
Z2 ' Boost ' G/F
Z2 ' Reduced ' G/F
(i) Group 1
(ii) Group 2
Z2 PH
Z2 PH
ZMO
P3049EN
Figure 19: Mutual Coupling example - zone 2 reach considerations
3.1.2.2 Zone setting KZ Residual compensation for Earth Fault Elements and KZ Angle
The reaches of the earth fault elements use residual compensation of the corresponding
phase fault reach. The residual compensation factors are:
kZ1 - For zone 1 and zone 1X;
kZ2 - For zone 2;
kZ3/4 - Shared by zones 3 and 4;
kZp - For zone p;
kZq - For zone q.
For earth faults, residual current either measured or derived as the vector sum of phase
current inputs (Ia + Ib + Ic) is assumed to flow in the residual path of the earth loop circuit.
Therefore, the earth loop reach of any zone must generally be extended by a multiplication
factor of (1 + kZ0) compared to the positive sequence reach for the corresponding phase
fault element. kZ0 is designated as the residual compensation factor, and is calculated as:
kZ0 Res. Comp, kZ0 = (Z
0
– Z
1
) / 3.Z
1
Set as a ratio.
kZ0 Angle, kZ0 = (Z
0
– Z
1
) / 3.Z
1
Set in degrees.
Where:
Z
1
= Positive sequence impedance for the line or cable;
Z
0
= Zero sequence impedance for the line or cable.
kZ0 CALCULATION DESCRIPTION
If we consider a phase to earth fault AN with analogue values VA and IA.
Using symmetrical components, VA is described as follows:
(1) VA = V1 + V2 + V0 = Z1I1 + Z2I2 + Z0I0

Table of Contents

Related product manuals