44x/EN ST/Hb6
-38 MiCOM P40 Agile
Menu text Default setting
Setting range
Step size
Min Max
GROUP 1 – CB FAIL & I<
CBF Ext Reset CB Open & I< I< Only, CB Open & I<, Prot Reset & I<,
Prot Reset or I<, Disable
Setting which de
termines the elements that will reset the circuit breaker fail time for external
protection function initiated circuit breaker fail conditions.
UNDER CURRENT I<
I< Current Set 0.05 × In 0.05 × In 3.2 × In 0.01 × In
Setting that determines the circuit breaker fail timer reset current for overcurrent based
protection circuit breaker fail initiation.