P44x/EN TD/
Hb6
Technical Data
(TD) 2
-14
MiCOM P40 Agile P442, P444
Zone Setting other parameters
Serial Compensated
Line: Enabled/Disabled
Overlap Z mode: Enabled/Disabled
Z1m Tilt Angle: 45° to +45° (step 1°)
Z1p Tilt Angle: 45° to +45° (step 1°)
Z2/Zp/Zq Tilt Angle 45° to +45° (step 1°)
Fwd Z Chgt Delay: 0 to 100ms (step 1ms)
Volt. Memory Validity: 0 to 10 s (step 10 ms)
Earth Current detection:
0 to 0.1×I1 (step 0.01×I1)
Fault locator:
KZm mutual Comp: 0 to 7 (step1)
KZm Angle: 0 to 360° (step 1°)
Load Blinder:
R< Blinder Lim: 0.001/In to 500/In
(step 0.001/In/)
Load/B Angle: 15° to 65° (step 1°)
Load Blinder V: 1 V to 70 V (step 0.5 V)
Distance Scheme setting
Program mode Standard or open scheme
Standard Modes:
Basic + Z1X,
POP Z1,
POP Z2,
PUP Z2,
PUP Forward,
BOP Z1,
BOP Z2.
POP = Permissive Overreach Protection
PUP = Permissive Underreach Protection
BOP = Blocking Overreach Protection
Fault type:
Phase to Ground,
Phase to Phase,
Both enabled.
Trip Mode:
Force 3 Pole,
1 Pole Z1 and Carrier Received (CR),
POP Z1 Z2 and CR.
Signal sent from a zone to the relays setting
(open scheme):
CsZ1 (Carrier sent by Z1),
CsZ2,
CsZ4.
Aided scheme on Carrier receipt “Dist CR”
(open scheme):
None,
PermZ1: Permissive Z1 (Z1 can trip without
waiting the end of tZ1 timout),
PermZ2,
PermFwd (forward),
Blocking Z1 (BlkZ1) (Z1 can only trip if a
Carrier is not received),
BlkZ2.
Additional time-delay for PUP Z2, PUP FWD,
POP Z1 and POP Z2 schemes:
0 to 1 s (stem 2 ms)
tReversal Guard: 0 to 0.15 s (step 2 ms)
Unblocking schemes (with permissive
schemes):
None,
Loss of Guard mode,
Loss of Carrier mode.