P54A/B/C/E
Appendix B - Settings and Signals
P54xMED-TM-EN-1
B29
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
February
March
April
May
June
July
August
September
October
November
December
[Indexed String]
Setting to specify the month in which daylight saving time adjustment ends
DST End Mins 08 2B 60
From 0 to 1425 in steps of 15
[Courier Number (time-minutes)]
Setting to specify the time of day in which daylight saving time adjustment ends. This is set relative to 00:00 hrs on the selected day when
time adjustment is to end
RP1 Time Zone 08 30 UTC
UTC
Local
[Indexed String]
Setting for the rear port 1 interface to specify if time synchronization received will be local or universal time co-ordinated
RP2 Time Zone 08 31 UTC
UTC
Local
[Indexed String]
Setting for the rear port 2 interface to specify if time synchronization received will be local or universal time co-ordinated
DNPOE Time Zone 08 32 UTC
UTC
Local
[Indexed String]
DNP3.0 over Ethernet versions only. Setting to specify if time synchronisation received will be local or universal time
co-ordinated.
Tunnel Time Zone 08 33 UTC
UTC
Local
[Indexed String]
Ethernet versions only for tunnelled courier. Setting to specify if time synchronization received will be local or universal time co-ordinated
CONFIGURATION
09
00
This column contains all the general configuration options
Restore Defaults 09 01 No Operation
No Operation
All Settings
Setting Group 1
Setting Group 2
Setting Group 3
Setting Group 4
[Indexed String]
Setting to restore a setting group to factory default settings.
To restore the default values to the settings in any Group settings, set the ‘restore defaults’ cell to the relevant Group number. Alternatively it
is possible to set the ‘restore defaults’ cell to ‘all settings’ to restore the default values to all of the IED’s settings, not just the Group settings.
The default settings will initially be placed in the scratchpad and will only be used by the IED after they have been confirmed by the user.
Note: Restoring defaults to all settings includes the rear communication port settings, which may result in communication via the rear port
being disrupted if the new (default) settings do not match those of the master station.
Setting Group 09 02 Select via Menu
Select via Menu
Select via PSL
[Indexed String]
Allows setting group changes to be initiated via Opto Input or via Menu
Active Settings 09 03 Group 1
Group 1
Group 2
Group 3
Group 4
[Indexed String]
Selects the active setting group.
Save Changes 09 04 No Operation
No Operation
Save