Appendix B - Settings and Signals 
 
 
 
MENU TEXT  COL  ROW  DEFAULT SETTING  AVAILABLE OPTIONS 
DESCRIPTION 
Copy From  09  05  Group 1 
Group 2 
Group 3 
Group 4 
Allows displayed settings to be copied from a selected setting group 
Copy To  09  06  No Operation 
Group 1 
Group 2 
Group 3 
Group 4 
Allows displayed settings to be copied to a selected setting group 
Setting Group 1  09  07  Enabled 
Enabled 
Settings Group 1.  If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the 
exception of this setting. 
Setting Group 2  09  08  Disabled 
Enabled 
Settings Group 2.  If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the 
exception of this setting. 
Setting Group 3  09  09  Disabled 
Enabled 
Settings Group 3.  If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the 
exception of this setting. 
Setting Group 4  09  0A  Disabled 
Enabled 
Settings Group 4.  If the setting group is disabled from the configuration, then all associated settings and signals are hidden, with the 
exception of this setting. 
Tripping Mode  09  0E  3 Pole 
1 and 3 Pole 
Current Diff  09  0F  Enabled 
Enabled 
To enable (activate) or disable (turn off) the Differential Protection: ANSI 87.  
To get the differential protection fully active, it is necessary also to enable the differential protection in the group. Note that Phase Diff 
setting and InterMiCOM64 Fiber setting are mutually exclusive as with Phase Diff enabled, the digital message exchanged has the structure 
of the differential message (i.e. currents are sent to the remote end, etc) and with interMiCOM64 Fiber the digital message exchanged has 
the structure and properties of the InterMiCOM64 Fiber. 
Overcurrent  09  10  Disabled 
Enabled 
To enable (activate) or disable (turn off) the Phase Overcurrent Protection function. I> stages: ANSI 50/51/67 
Neg Sequence O/C  09  11  Disabled 
Enabled 
To enable (activate) or disable (turn off) the Negative Sequence Overcurrent Protection function. I2> stages: ANSI 46/67 
Broken Conductor  09  12  Disabled 
Enabled 
To enable (activate) or disable (turn off) the Broken Conductor function. I2/I1> stage: ANSI 46