P54A/B/C/E
Appendix B - Settings and Signals
P54xMED-TM-EN-1
B31
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the back up Earth Fault Protection function. IN >stages: ANSI 50N/51N/67N
Earth Fault 09 13 Enabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the back up Earth Fault Protection function. IN >stages: ANSI 50N/51N/67N
SEF/REF Prot'n 09 15 Disabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Sensitive Earth Fault/Restricted Earth fault Protection function.
ISEF >stages: ANSI 50N/51N/67N. IREF>stage: ANSI 64.
Residual O/V NVD 09 16 Disabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Residual Overvoltage Protection function. VN>stages: ANSI 59N
Thermal Overload 09 17 Disabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Thermal Overload Protection function. ANSI 49.
Volt Protection 09 1D Disabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Voltage Protection (under/overvoltage/remote) function. V<, V>, Cp V> stages: ANSI 27/59/59R.
Freq Protection 09 1E Disabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Frequency Protection (under/over frequency) function. F<, F> stages: ANSI 81.
df/dt Protection 09 1F Disabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Rate of change of Frequency Protection function. df/dt> stages: ANSI 81.
CB Fail 09 20 Disabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Circuit Breaker Fail Protection function: ANSI 50BF.
Supervision 09 21 Enabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Supervision (VTS & CTS) functions: ANSI 47/27/46.
System Checks 09 23 Disabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the System Checks (Check Sync. and Voltage Monitor) function: ANSI 25.
Auto-Reclose 09 24 Disabled
Disabled
Enabled
[Indexed String]
To enable (activate) or disable (turn off) the Auto-reclose function. ANSI 79.
Input Labels 09 25 Visible
Invisible
Visible
[Indexed String]
Sets the Input Labels menu visible further on in the IED settings menu.
Output Labels 09 26 Visible
Invisible
Visible
[Indexed String]
Sets the Output Labels menu visible further on in the IED settings menu.
CT & VT Ratios 09 28 Visible
Invisible
Visible
[Indexed String]
Sets the Current & Voltage Transformer Ratios menu visible further on in the IED settings menu.