Menu Text  Default Setting 
Setting Range 
Step Size 
Min.  Max. 
SNTP Server 2  Data 
Displays the IP address of the secondary SNTP server. 
IEC61850 SCL 
IED Name  Data 
8 character IED name, which is the unique name on the IEC 61850 network for the IED, 
usually taken from the SCL (Substation Configuration Language for XML) file. 
IEC61850 GOOSE 
GoEna  00000000  00000000  11111111  1 
GoEna (GOose ENAble) is a setting to enable GOOSE (Generic Object Orientated 
Substation Event, for high-speed inter-device messaging) publisher settings. This setting 
enables (“1”) or disables (“0”) GOOSE control blocks from 08 (1
st
 digit) to 01 (last digit). 
Test Mode  00000000  00000000  11111111  1 
The Test Mode cell allows the test pattern to be sent in the GOOSE message, for example 
for testing or commissioning.  
The setting enables (“1”) or disables (“0”) test mode for GOOSE control block from 08 (1
st
 
digit) to 01 (last digit). 
Once testing is complete the cell must be set back to ‘Disabled’ to restore the GOOSE 
scheme back to normal service. 
Ignore Test Flag  No  No, Yes 
When set to ‘Yes’, the test flag in the subscribed GOOSE message is ignored, and the 
data treated as normal. 
 
1.3.13   “Control I/P (input) labels” column (P741 / P743 only) 
This column is visible when the “Control I/P Labels” setting (“Configuration” column) = 
“visible”. 
Menu Text  Default Setting  Setting Range  Step Size 
CTRL I/P LABELS 
Control Input 1  Control Input 1  16 Character Text 
Setting to change the text associated with each individual control input. This text will be 
displayed when a control input is accessed by the hotkey menu, or it can be displayed in 
the programmable scheme logic. 
Control Input 2 to 32 
Control Input 
2 to 32 
16 Character Text 
As “Control input 1” for control inputs 2 to 32.