P74x/EN ST/N
1, P742, P743 
(ST) 4-
 
1.2.1.2  Sensitive earth fault element  
The sensitive earth fault element is included for high impedance earthed systems and has 
bias current control to guarantee stability under external faults or when there are significant 
errors in the measurement CTs. The element is usually disabled for effectively earthed 
systems with low impedance or solid earthing.  
Menu Text  Default Setting 
Setting Range 
Step Size 
Min.  Max. 
DIFF BUSBAR PROT 
Diff Earth Fault (Diff busbar protection menu second part) 
Diff Earth Fault  Disabled  Enabled/Disabled 
To enable (activate) or disable (turn off) the differential earth fault protec
activated, the following functions are accessible. 
IBiasPh>Cur. 
2000 A  50 A  30.000 A  10 A 
Setting that determines the Earth fault element blocking characteristic 
CZ Parameters 
Earth Slope k
N
CZ  10%  0%  90%  1% 
Slope angle setting for the check zone biased differential Earth element. 
I
DN
CZ>2 Current 
1200 A  10 A  30.000 A  10 A 
Setting that determines the minimum differential operating current for the check zone 
biased differential Earth element 
Zone Parameters 
Earth Slope k
N
2  10%  0%  90%  1% 
Slope angle setting for all discriminating zone biased differential Earth elements 
I
DN
>2 Current 
1000 A  10 A  30.000 A  10 A 
Setting that determines the minimum differential operating current for all the discriminating 
zone biased differential Earth elements 
Common 
I
DN
>1 Current 
100 A  10 A  500 A  10 A 
Setting for the Neutral circuitry fault monitoring characteristic for the minimum pickup 
Earth slope k
N
1  10%  0%  50%  1% 
Slope angle setting for the Neutral circuitry fault monitoring characteristic. 
I
DN
>1 Alarm Timer 
5.0s  0.0s  600.0s  0.1s 
Setting for the Neutral circuitry fault monitoring minimum pickup timer