Na7 
 
-
 
MiCOM P741, P742
 
Table below shows operation depending on the thresholds' status. 
I
D
>1  k1.I
bias
  I
D
>2 
Status  Operation 
0  0  0  Normal  No operation 
1  0  0  Normal  No operation 
0  1  0  Normal  No operation 
1  0  1 
circuitry fault 
External fault with CT saturation or 
block circuitry fault alarm after t
CF
 
1  1  0  Circuitry fault  Block and circuitry fault alarm after t
CF
 
1  1  1  Internal fault  Trip 
TABLE 1: OPERATION CONDITIONS 
1.2.5  Signal Quality 
An additional check is carried out to confirm that the signals used to determine the previous 
criteria are satisfactory. 
This includes checking for CT saturation conditions (information from peripheral unit, refer to 
Section 2.1), that no plant discrepancies exist (via check zone as discussed earlier), and that 
a change (increase or loss) in current flow has been detected by at least two peripheral units 
(I detection). The latter condition is used, as internal or external faults will cause a change 
in levels in at least two circuits whereas, a CT fail only affect a single circuit’s level (faulty 
CT). 
Note:   This condition is used only when there is no dead bus condition. 
When a trip is issued for a bus zone by the central unit a signal is sent to all peripheral units 
associated (or not) with the faulted bus zone. The peripheral units associated with the faulted 
zone can carry out a further local confirmation via  local Overcurrent protection, I>BB or 
I
N
>BB, before allowing a trip to take place.  
1.2.6  Tripping Criteria 
Before a trip signal is issued 4 trip criterions at the top level, i.e. the Central Unit, and 1 
(optional) at the local level, i.e. the Peripheral Units, must be met. 
These criterions are: 
Top level (Central Unit) 
    Instantaneous criteria: 
•  Bias characteristic ( I
diff
 > (I
D
>2)) and Differential current setting are 
exceeded (I
diff
> k2 I
bias
) for the zone for 2 consecutive samples 
•  Bias characteristic ( I
diff
 > (I
D
CZ>2)) and Differential current setting are 
exceeded (I
diff
> kCZ I
bias
) for the check zone for 2 consecutive samples 
•  No CT saturation 
•  Signal quality (CT supervision, , AD converter, etc…) 
    Delayed criteria: 
•  Bias characteristic ( I
diff
 > (I
D
>2)) and Differential current setting are 
exceeded (I
diff
> k2 I
bias
) for the zone for at least 1 sample 
•  Bias characteristic ( I
diff
 > (I
D
CZ>2)) and Differential current setting are 
exceeded (I
diff
> kCZ I
bias
) for the check zone for at least 1 sample 
•  Bias characteristic ( I
diff
 > (I
D
>2)) and Differential current setting are not 
exceeded (I
diff
> k2 I
bias
) for the zone for at least 1 sample in the 4 following 
samples