x/EN MR/Na7 
 
Measurements and Recording 
-
 
MiCOM P74
 
 
 
VIEW RECORDS 
Description 
LCD Reference 
Start Elements  Start I>1, Start I>2, Start I>2BB, Start I>BB, Start IN>1, Start 
IN>2, Start IN>2BB, Start IN>BB 
Trip Elements 
Trip I>1, Trip I>2, Trip IN>1, Trip IN>2, Trip 87BB, Trip 
CBFail tBF1, Trip CBFail tBF2, Trip CBFail tBF3, Trip CBFail 
tBF4, Trip 50BF (CU), Manual Trip zone, Trip 87BB block, 
Dead Zone Trip 
Time Stamp  Time and date of fault recorder start 
Fault Alarms  Yes, No 
System Frequency  50.00 Hz, 60.00 Hz, 
Relay Trip Time  Delay between reception of signal and end of trip on PU 
IA  Feeder phase A current 
IB  Feeder phase B current 
IC  Feeder phase C current 
IN  Feeder phase N current 
Select Maint. 
Setting range from 0 to 9.  This selects the required 
maintenance report from the possible 10 that may be 
A value of 0 corresponds to the latest report and so on. 
Maint. Text 
Up to 16 Character description of the occurrence (refer to 
following sections). 
Maint. Type/Main Data 
These cells are numbers representative of the occurrence.  
They form a sp
ecific error code which should be quoted in 
any related correspondence to Report Data. 
Reset Indication 
Either Yes or No.  This serves to reset the trip LED 
indications provided that the relevant protection element has 
reset, to reset all LED and relays latched in the PSL, and to 
reset the latched alarms. 
For extraction from a remote source via communications, refer to the SCADA 
Communications section (P74x/EN CT), where the procedure is fully explained. 
2.3  Types of event 
An event may be a change of state of a control input or output relay, an alarm condition, 
setting change etc.  The following sections show the various items that constitute an event: 
2.3.1  Change of state of opto-isolated inputs 
If one or more of the opto (logic) inputs has changed state since the  last time that the 
protection algorithm ran, the new status is logged as an event.  When this event is selected 
to be viewed on the LCD, three applicable cells will become visible as shown below: 
Time & date of event 
“LOGIC INPUTS #” 
“Event Value  0101010101010101” 
Where # = 1 or 2 depending upon which group of 16 opto inputs is selected.  In the case of 
P74x relay, however, the value will always be “1” as it is impossible to have more than 16 
opto inputs.