P74x/EN ST/N
1, P742, P743 
(ST) 4-
 
Menu Text  Default Setting 
Setting Range 
Step Size 
Min.  Max. 
Ι
N
>1 Current Set  0.30*Ι
n 
0.10*Ι
n
  32.00*Ι
n
  0.01*Ι
n
 
Pick-up setting for the first stage earth fault element. 
Ι
N
>1 Time Delay 
1.00s  0.00s  100.00s  0.01s 
Time-delay setting for the first stage definite time element. 
Ι
N
>1 TMS 
1.000  0.025  1.200  0.025 
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT 
characteristic.  
Ι
N
>1 Time Dial 
7.0  0.5  15.0  0.1 
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT 
curves. 
Ι
N
>1 Reset Char 
DT  DT/Inverse 
Setting to determine the type of reset/release characteristic of the IEEE/US curves. 
Ι
N
>1tReset 
0.0  0.0  100.0  0.1 
Setting to determine the reset/release time for definite time reset characteristic. 
Ι
N
>2 Function 
Disabled 
Disabled / 87BBP&N blocking / High Set I>2 / I>2 & 
87BBP&N / 87BB/P blocking / 87BB/N blocking / 
I>2 & 87BB/P / I>2 & 87BB/N 
Setting to en
able or disable the second stage definite time element. If the function is 
disabled, then all associated settings with the exception of this setting, are hidden. 
The overcurrent can be used as high set overcurrent, to block the 87BB protection for 
phase an
d earth fault element (87BBO&N blocking) , only the 87BB phase element 
(87BB/P blocking), only the 87BB SEF element (87BB/N blocking), or a combination of the 
different functions 
Ι
N
>2 Current Set  20.00* Ι
n
  0.10*Ι
n
  32.00* Ι
n
  0.01* Ι
n
 
Pick-up setting for the second stage earth fault element. 
Ι
N
>2 Time Delay 
1.00s  0.00s  10.00s  0.01s 
Setting for the operating time delay for the second stage earth fault element. 
Block Drop-Off  0.3s  0.2s  6s  0.1s 
Adjust the differential busbar protection (87BB) blocking function during drop-off time from 
200ms to 6s. 
 
1.2.7  Circuit breaker fail and undercurrent function (“CB Fail” column – P742/P743) 
This function consists of two-stage circuit breaker fail functions that can be initiated by: 
•  Internal protection element initiation. 
•  External protection element initiation. 
For current-based protection, the reset condition is based on undercurrent operation to 
determine that the CB has opened. For the non-current based protection, the reset criteria 
may be selected by means of a setting for determining a CB Failure condition. 
It is common practice to use low set undercurrent elements in protection relays to indicate 
that circuit breaker poles have interrupted the fault or load current, as required.