MiCOM P741, P742
 
4.  OPERATION OF NON PROTECTION FUNCTIONS 
4.1  Programmable scheme logic 
4.1.1  Level settings 
Name  Range  Step Size 
Time delay t  0-14400000ms  1ms 
4.1.2  Accuracy  
Output conditioner timer 
Setting ±2% or 50ms whichever is greater  
Dwell conditioner timer 
Setting ±2% or 50ms whichever is greater  
Pulse conditioner timer  
Setting ±2% or 50ms whichever is greater  
4.2  IRIG-B signal (P741) only 
If a satellite time clock signal conforming to IRIG-B is provided and the P741 relay has the 
optional IRIG-B port fitted, the satellite clock equipment should be energised. 
In the event of the auxiliary supply failing, with a battery fitted in the compartment behind the 
bottom access cover, the time and date will be maintained. Therefore, when the auxiliary 
supply is restored, the time and date will be correct and not need to be set again. 
The P741 synchronises all peripheral units (P742/P743) every 10s and during the powering 
on of the scheme. 
4.3  Differential current display 
When the differential currents are low, it is possible to force to 0 the value of these 
differential currents displayed in the column MEASUREMENT 1 & MEASUREMENT 2 . 
When the differential currents of a zone are all lower than the threshold (on the 3 phases), 
the currents displayed are forced to 0.