-10  MiCOM P74
 
 
2.1.1.3.1 Sub-station features 
8 values have to be known: 
1.  Number of independent bus 
2.  Minimum load current in a feeder 
3.  Maximum load current in a feeder 
4.  Maximum load current in a bus 
5.  Biggest CT primary winding 
6.  Minimum phase to phase short-circuit value in a bus 
7.  Minimum phase to ground short-circuit value in a bus 
8.  Maximum phase to ground short-circuit value in a bus 
2.1.1.3.2 “Idiff_Ibias_SDEF_HighImp” Setting calculation spreadsheet 
Enter in the Idiff_Ibias_SDEF spreadsheet the 8 values here above listed and you’ll be able 
to choose the 9 values hereafter listed. 
2.1.1.3.3 SDEF Busbar Protection 
15 values have to be entered: 
1.  ID>1 (from 5 A to 500 A (primary value)) as high as possible 
2.  Slope k1 (ID>1) (from 0% to 50%), recommendation is 5%. 
3.  ID>2 (from 50 A to 50000 A (primary value)) 
4.  Slope k2 (ID>2) (from 20% to 90%), recommendation is 65%. 
5.  IDCZ>2 (from 50 A to 50000 A (primary value)) as low as possible 
6.  Slope kCZ (IDCZ>2) (from 0% to 90%), recommendation is 30%. 
7.  ID>1 Alarm Timer (from 0 to 100 s) shall be greater than the longest protection time 
(such as line, overcurrent, etc…) 
8.  Current IbiasPh> Cur. (from 50 A to 50000 A (primary value)) as low as possible