The following lines give the default settings for digital inputs 2 to 32 
Menu Text  Default Setting  Explanation 
Digital Input 2  Circt Flt Lck z2  Circuitry fault blocks zone 2 digital channel  
Digital Input 3  87BB Blocked  digital 87BB Blocked channel  
Digital Input 4  Ext Start DR 
External start of the disturbance recorder 
digital channel  
Digital input 5  Earth Fault  Earth fault digital channel  
Digital input 6  Fault Check zone  Fault Check zone digital channel  
Digital input 7  Fault phase A  Fault phase A digital channel  
Digital input 8  Fault phase B  Fault phase B digital channel  
Digital input 9  Fault phase C  Fault phase C digital channel  
Digital input 10  Flt 87BB zone 1  Fault 87BB zone 1 digital channel  
Digital input 11  Flt 87BB zone 2  Fault 87BB zone 2 digital channel  
Digital input 12  Manual Start DR 
Manual start of the disturbance recorder 
digital channel  
Digital input 13  Topo/Set Changed  Topology or setting changed digital channel  
Digital input 14  Trip Manual zone  Manual trip of the zone digital channel  
Digital input 15  Trip 50BF zone 1  Trip 50BF zone 1 digital channel  
Digital input 16  Trip 50BF zone 2  Trip 50BF zone 2 digital channel  
Digital input 17  Trip 87BB zone 1  Trip 87BB zone 1 digital channel  
Digital input 18  Trip 87BB zone 2  Trip 87BB zone 2 digital channel  
Digital input 19  PU Error Lck z1  PU error blocks zone 1 digital channel  
Digital Input 20  PU Error Lck z2  PU error blocks zone 2 digital channel  
Digital Input 21 to 32  Unused   
The digital channels may be mapped to any of the opto isolated inputs or output contacts, 
in addition to a number of internal relay digital signals, such as protection starts, LEDs etc. 
 
Menu Text  Default Setting 
Setting Range 
Step Size 
Min.  Max. 
DISTURB. RECORDER 
Manual Trigger  No  Yes or No 
Command to trigger the disturbance recorder. The differential and bias currents recorded 
depend of the following settings Zone to record. 
Zone to record  Zone 1   Zone 1 to zone 8 
Any one of the 8 zones can be recorded upon a manual triggering. If 2 or more zones are 
selected, the check zone will be recorded