pplication Notes 
 
P74x/EN AP/N
1, P742, P743  (AP) 6-
 
•  when all these buses are independent (bus sectionalizers open) 
•  the maximum load is on all the buses (biggest bias current) 
•  The internal short-circuit value is minimum. 
Feeder Feeder Feeder
Feeder
Feeder
Feeder
Feeder
Feeder
Feeder
P0871ENa
Max Load
Max Load
 
During the internal fault: 
•  the bias current is: Icc min (1 bar) + (n-1) x IloadMax (1 bar) 
•  the differential current is: Icc min (1 bar) 
Thus the biggest slope for the Check Zone to detect the fault is: 
Icc min (1 bar) 
((Independent bars - 1) x IloadMax (1 bar)) + Icc min (1 bar) 
If for example: 
There are 3 buses and Icc min = IloadMax, the slope must be below 33% 
For a one and half breaker scheme there are: 
•  2 bars (Independent bars) 
•  A minimum internal short-circuit value (Icc min (1 bar)) 
•  A maximum load for a bar (IloadMax (1 bar)). 
Feeder
Feeder Feeder
Feeder
Feeder
Feeder
lload
lload
lload
lload
P0872ENa
 
The worst case is: 
•  when the is split in 2 and goes as well through the opposite bar