Menu Text  Default Setting  Available Settings 
Setting Group  Select via Menu 
Select via Menu  
Select via Optos 
Allows setting group changes to be initiated via Opto Input or via Menu.  
Active Settings  Group 1 
Group 1, Group 2, Group 3,   
Group 4 
Selects the active setting group. 
Save Changes  No Operation  No Operation, Save, Abort 
Saves all relay settings. 
Copy from  Group 1  Group 1, 2, 3 or 4 
Allows displayed settings to be copied from a selected setting group.  
Copy to  No Operation 
No Operation 
Group 1, 2, 3 or 4 
Allows displayed settings to be copied to a selected setting group (ready to paste). 
Setting Group 1  Enabled  Enabled or Disabled 
If the setting group is disabled from the configuration, then all associated settings and 
signals are hidden, with the exception of this setting (paste). 
Setting Group 2 (as above)  Disabled  Enabled or Disabled 
Setting Group 3 (as above)  Disabled  Enabled or Disabled 
Setting Group 4 (as above)  Disabled  Enabled or Disabled 
Busbar Option  Invisible  Visible / Invisible 
Sets the Busbar Option menu visible further on in the relay settings menu. 
Diff Busbar Prot  Enabled  Enabled or Disabled 
To enable (activate) or disable (turn off) the Differential Busbar Protection function  
(ANSI 87BB).  
Input Labels  Visible  Invisible or Visible 
Sets the Input Labels menu visible further on in the relay settings menu. 
Output Labels  Visible  Invisible or Visible 
Sets the Output Labels menu visible further on in the relay settings menu. 
Recorder Control  Visible  Invisible or Visible 
Sets the Record Control menu visible further on in the relay settings menu. 
Disturb. Recorder  Visible  Invisible or Visible 
Sets the Disturbance Recorder menu visible further on in the relay settings menu. 
Measure't. Set-up  Visible  Invisible or Visible 
Sets the Measurement Setup menu visible further on in the relay settings menu. 
Comms. Settings  Invisible  Invisible or Visible 
Sets the Communications Settings menu visible further on in the relay settings menu. 
These are the settings associated with the 1
st
 and 2
nd
 rear communications ports. 
Commission Tests  Visible  Invisible or Visible 
Sets the Commissioning Tests menu visible further on in the relay settings menu. 
Setting Values  Primary  Primary or Secondary 
This affects all protection settings that are dependent upon CT and VT ratios.