P74x/EN ST/N
1, P742, P743 
(ST) 4-
 
MENU TEXT  Default Setting  Available Settings 
CONFIGURATION   
Copy to   No Operation  No Operation / Group 1 / Group 2 
Group 3 / Group 4 
Allows displayed settings to be copied to a selected setting group (ready to paste). 
Setting Group 1  Enabled  Enabled/Disabled 
If the setting group is disabled from the configuration, then all associated settings and 
signals are hidden, with the exception of this setting (paste). 
Setting Group 2  Disabled  Enabled/Disabled 
Setting Group 3  Disabled  Enabled/Disabled 
Setting Group 4  Disabled  Enabled/Disabled 
Dead Zone Prot  Enabled  Enabled/Disabled 
To enable (activate) or disable (turn off) the Dead Zone Protection function. 
BB Trip Confirm  Disabled  Enabled/Disabled 
To enable (activate) o
r disable (turn off) the Busbar Trip order confirmation on an 
overcurrent function to allow to trip the breaker. 
Overcurrent Prot  Disabled  Enabled/Disabled 
To enable (activate) or disable (turn off) the Phase Overcurrent Protection function. 
ANSI 50P/51. 
Earth Fault Prot   Disabled  Enabled/Disabled 
To enable (activate) or disable (turn off) the Earth Overcurrent Protection function. 
ANSI 50N/51N.  
CB Fail & I<  Disabled  Enabled/Disabled 
To enable (activate) or disable (turn off) the Circuit Breaker Fail Protection functions.  
ANSI 50BF. 
Input Labels  Visible  Visible/Invisible 
Sets the Input Labels menu visible further on in the relay settings menu. 
Output Labels  Visible  Visible/Invisible 
Sets the Output Labels menu visible further on in the relay settings menu. 
CT & VT Ratios   Visible  Visible/Invisible 
Sets the Current & Voltage Transformer Ratios menu visible further on in the relay settings 
menu. 
Recorder Control  Visible  Visible/Invisible 
Sets the Record Control menu visible further on in the relay settings menu. 
Disturb Recorder  Visible  Visible/Invisible 
Sets the Disturbance Recorder menu visible further on in the relay settings menu. 
Measure't Setup  Visible  Visible/Invisible 
Sets the Measurement Setup menu visible further on in the relay settings menu. 
Comms Settings  Invisible  Visible/Invisible 
Sets the Communications Settings menu visible further on in the relay settings menu. 
Commission Tests  Visible  Visible/Invisible 
Sets the Commissioning Tests menu visible further on in the relay settings menu.