ADV200 SP • Quick start up guide - Specification and installation 27

Strip T2 (top)
Termi-
nal
Designation Function Max
R21
COM Digital
output 2
Common reference for digital output 2 (Relay 2) -
R24 Digital output 2 Programmable digital relay output 2 (NO). Default = Drive ready 250
Vac - 30Vdc / 2A
5 Analog output 1 Analog output 1. Default = Null (not assigned) ±12,5 V (typical ±10 V / 5 mA)
6 Analog output 2 Analog output 2. Default = Null (not assigned)
- voltage (default):
±12,5 V (typical ±10V/5mA)
- current (set by S3 switch): 0...20mA or
4...20mA (setting by PAR 1848, 15 - ANALOG
OUPUTS menu)
C1
COM Analog
output
Common reference for analog outputs and ±10V potential voltage reference -
7 Digital input E Digital input E. Default = Digital input E mon (Enable) 5mA @ +24V (+30V max)
8 Digital input 1 Digital input 1. Default = FR forward src, PAR 1042 5mA @ +24V (+30V max)
9 Digital input 2 Digital input 2. Default = FR reverse src, PAR 1044 5mA @ +24V (+30V max)
10 Digital input 3 Digital input 3. Default = Null (not assigned) 5mA @ +24V (+30V max)
11 Digital input 4 Digital input 4. 5mA @ +24V (+30V max)
12 Digital input 5 Digital input 5. 5mA @ +24V (+30V max)
C2
COM Digital
inputs
Common reference for digital inputs -
C3 0V 24 OUT Reference point for +24V OUT -
S3 + 24V OUT +24V supply for IO 150 mA (Resettable fuse), ±10 %
Strip T1 (bottom)
Termi-
nal
Designation Function Max
R11
COM Digital
output 1
Common reference for digital output 1 (Relay 1) -
R14 Digital output 1 Programmable digital relay output 1 (NO). Default = Drive OK 250
Vac - 30Vdc / 2A
1
Analog input 1
Programmable / configurable analog differential input.
Signal: terminal 1. Reference: terminal 2.
Default = Ramp ref 1 src
- voltage (default):
±12,5 V (typical ±10V/1mA)
- current (set by switches S1-S2):
0...20mA or 4...20mA (set by PAR 1502 or
1552, 14 - ANALOG INPUTS menu)
- input impedance = 10 kΩ
2
3
Analog input 2
Radiation sensor analog input.
Signal: terminal 3. Reference: terminal 4.
Default = Irrad Sens src
4
S1+ +10 V Voltage reference +10V; reference point: C1 terminal +10 V ±1% / 10 mA
S1- - 10V Analog output -10V; reference point: C1 terminal -10 V ±1% / 10 mA
13 Digital output 3 Digital output 3. Default = Speed is 0 delay +24 V / 20 mA (typ), 40 mA (max)
14 Digital output 4 Digital output 4. Default = Ref is 0 delay +24 V / 20 mA (typ), 40 mA (max)
IS1
PS Digital
output
Digital outputs 3 / 4 power supply -
IC1
COM Digital
output
Common reference for digital outputs 3 / 4 -
IC2 0V 24 EXT Reference for regulation card 24V external supply -
IS2 + 24V EXT External supply of regulation card +24V ±10% / 1A
+24V

It is not suitable to power supply the regulation card only through a unique rectier and capacitive lter.
La tension de + 24Vdc utilisée pour alimenter extérieurement la carte de régulation doit être stabiliséeet avec
une tolérance de ±10% ; absorption maximum de 1A. Les alimentations obtenues avec les seules redresseur e
ltre capacitive ne sont pas appropriées.
Caution

Table of Contents