EasyManua.ls Logo

gefran ADV200 SP Series - Page 75

gefran ADV200 SP Series
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ADV200 SP • Quick start up guide - Specification and installation 75
Sizes
f
sw
Switching frequency
Derating factor
Default Higher
K
t KAlt Kf (4)
(2) (3)
2 kHz 4 kHz 6 kHz 8 kHz 10 kHz 12 Hz
1030 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.55 0.4
1040 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.55 0.4
1055 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.6 0.5
2075 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.6 0.5
2110 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.6 0.5
2150 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.6 0.5
3185 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.6 0.5
3220 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.6 0.5
3300 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.6 0.5
4370 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.6 0.5
4450 4 6, 8, 10, 12 0.9 1.2 1 1 0.85 0.7 0.6 0.5
4550 4 6, 8 0.9 1.2 1 1 0.85 0.7 0 0
5750 4 6, 8 0.9 1.2 1 1 0.85 0.7 0 0
5900 4 6, 8 0.9 1.2 1 1 0.85 0.7 0 0
51100 4 6, 8 0.9 1.2 1 1 0.85 0.7 0 0
61320 4 6, 8 0.9 1.2 1 1 0.85 0.7 0 0
61600 4 6, 8 0.9 1.2 1 1 0.85 0.7 0 0
Note! In Light Duty mode the switching frequency is set at 4 kHz for sizes up to 61600.
If, in the Heavy duty mode, the factory setting of Switching freq mode (PAR: 568) is changed from 0=Fixed to 1=Vari
-
able, the switching frequency is controlled by the temperature of the drive heat sink and the output frequency. For further
information see the Functions and Parameters manual, menu 4.9.
Installation altitude above
sea level
K
t Output Current derating factor at Ambient Temperature of:
20°C 25°C 30°C 35°C 40°C 45°C 50°C
0 … 1000 m 1 0.95 0.90
Input voltage derating factor
Kv
2
(
6)

Figure 9.6.1: K2 
0 1000 2000 3000 4000
0.7
0.8
0.9
1.0
Installation Altitude a.s.l. (meters)
Derating Kv
Installation
altitude
K
V2 Derating factor (6)
Mains voltage [V]
m (s.l.m.) 380
VAc 400VAc 415VAc 440VAc 460VAc 480VAc
≤ 2000 100% 100% 100% 100% 100% 100%
≤ 2250 100% 100% 100% 100% 100% 97%
≤ 2500 100% 100% 100% 100% 98% 94%
≤ 2750 100% 100% 100% 100% 96% 92%
≤ 3000 100% 100% 100% 97% 93% 89%
≤ 3250 100% 100% 99% 94% 90% 86%
≤ 3500 100% 100% 96% 91% 87% 83%
≤ 3750 100% 96% 93% 88% 84% 80%
≤ 4000 98% 93% 90% 85% 81% 78%

Caution

Table of Contents

Related product manuals