Version 2.4 Page 59
20 11 0026 :
Read Literal
Value
05
Read Final Value
in Hex
11
Commands
Write Final Value 12
Gross Weight 0026
Net Weight 0027
Target High 0171
Target Low 0172
Keypress 0008
System Status 0021
Registers
System Error 0022
Value to write (in hexadecimal)
The indicator will respond with a message similar to the following:
9F110026:00000127
Where the value after the ":" (00000127) is the hexadecimal value of the gross weight without any
decimal places or units. In decimal, this value is 295.
Register Description Code Example
Version of the protocol 0001 V1.0
Copyright message 0002 © GSE 2006
Model of indicator 0003 250
Software version 0004 V1.20
Indicator serial number 0005 3123456
Contents of LCD display memory 0009 0100005B6D3F
Save settings command 0010
Start of menu definitions 0011
OIML calibration counter 0012 00000033
NTEP calibration counter 0013 C.00011
NTEP configuration counter 0014 F.00010
Counts each new reading 0020 00169196
Indicator status 0021 00000200
Indicator error status 0022 00000000
Absolute signal in mV/V 0023 00006187
Displayed weight reading 0024 000005DC
Gross or Net weight 0025 000005DC
Gross weight 0026 000005DC
Net weight 0027 000001F4
Tare weight 0028 000003E8
Peak held weight 0029 000009C4
Manual held weight 002A 00000000
Total weight reading 002B 000009C4
Livestock weight 002C 0000001F4
Index for first register data 0042 00000001
Index for second register data 0043 00000002
Index for third register data 0044 00000005