Modbus
Sultan Acoustic Wave Series
37
Extended Parameters (Read/Write) *MUST Read/
Write SINGLES-NOT BLOCKS*:
40059 - DISPLAY UNITS
3-Millimetres
4-Centimetres
5-Metres
6-Feet
7-Inches
40014 - FAILSAFE MODE
0 - 3.5mA
1 - 3.8mA
2 - 20.2mA
3- Last Known
4 - 4.0mA
5 - 20.0mA
40015 - FAILSAFE TIME (seconds)
40016 - APPLICATION TYPE
0 - Liquid
1 - Solid
2 - Slurry
3 - Position
40017 - FILL RATE (metres per hour/10)
40018 - EMPTY RATE (metres per hour/10)
40019 - DISPLAY MODE
1 - Volume
2 - Flow
3 - Material %
4 - Material
5 - Space
6 - Differential Output
7 - Average Material
40032 - OFFSET (mm)
40020 - LOCK CODE
40021 - FILL DAMPING
40022 - EMPTY DAMPING
40063 - ANALOG
0 - 4-20mA (4mA low, 20mA high - standard)
1 - 20-4mA (20mA low, 4mA high - inverted)
40447 - GAIN parameter setting in %/7.5
40448 - GAIN STEP in %/7.5
40449 - DISTANCE STEP (mm)
40450 - THRESHOLD in Volts/100
40451 - BLANKING (mm)
40452 - EMPTY DISTANCE (mm)