1-92
TROUBLESHOOTING
■ Activating Condition of Protection Control Code
For following the conditions as the temperature change, etc., the control of frequency, etc. is performed to
prevent the abnormal conditions by the protection control.
The activating conditions of protection control are shown in the table below.
Code Activating Condition Remarks
P01
 Compression Ratio>
9 => Frequency Decrease
 (Pd/(Ps+1.3))<
2.2 => Frequency Increase
 Ps: Suction Pressure of
 Compressor
P02  Pd>
2.4MPa => Frequency Decrease
 Pd: Discharge Pressure of
 Compressor
P03
 Inverter Output Current>
25A (220V),
 14A (380, 415V) => Frequency Decrease
 - 
P04
 Inverter Fin Temperature>
94
o
C
 => Frequency Decrease
 - 
P05
 Temperature at the top of compressor is high
 => Frequency Increase
 (Maximum temperature is different
 depending on the frequency.)
 - 
P06
 Low-Pressure is Excessively Low
 => Frequency Increase
 (Minimum pressure is different
 depending on the ambient temperature.)
 - 
 For
 16, 20HP
 When Switching
 ∆P<0.5MPa => Frequency Increase
 ∆P>1.3MPa => Frequency Decrease
 For
 24, 30HP
 When Switching
 ∆P<1.0MPa => Frequency Increase
 ∆P>2.1MPa => Frequency Decrease
 For
 5 to 20HP
 Frequency less than 40Hz is maintained for
 more than 1 hour. => Frequency>
40Hz
 For
 24, 30HP
 Frequency less than 120Hz at cooling
 (150Hz at heating) is maintained for more
 than 1 hour => Frequency>
120Hz at cooling
 (150Hz at heating)
P09
 Pd<
0.69MPa => Frequency Increase
                  (When Cooling Operation)
 Pd<
1.57MPa => Frequency Increase
                  (When Heating Operation)
 Pd: Discharge Pressure of
 Compressor
P0A
 Running Current for Comp.>
Setting Value
 => Frequency Decrease
 Setting Value:
 Upper limit of total running
 current is set 80%, 70% and
 60% at normal operation
 using input on PCB.
P11  Compression Ratio (Pd/(Ps+1.3)<1.8)
 When activating 3 times in an
 hour, "43" alarm is indicated.
P12  Ps>0.9MPa
 When activating 3 times in an
 hour, "44" alarm is indicated.
 For
 5 to 20HP
 Ps>2.7MPa
 (In case of 20 to 30Hz: Pd>2.5MPa)
 For
 24, 30HP
 Ps>2.7MPa
P14
 Current>
Maximum Value(*1),
 or Current<0.9A
 When activating 3 times in an
 hour, "39" alarm is indicated.
P15
 In Case of
 Ps>0.02MPa over 12 minutes,
 Discharge Gas Temperature>
132
o
C over
 10 minutes
 or Discharge Gas Temperature>
140
o
C over
 5 seconds
 When activating 3 times in
 30 minutes, "47"(Ps) or "08"
 (Discharge Gas) alarm is
 indicated.
 For
 5 to 20HP
 Discharge Gas SUPERHEAT less than
 10 deg. is maintained for an hour.
 For
 24, 30HP
 Discharge Gas SUPERHEAT less than
 10 deg. is maintained for 30 minutes.
P17  Inverter Trip Retry
 Automatic Stoppage of Transistor Module,
 Activation of Electronic Thermal
 or Abnormal Current Sensor
 When activating 3 times in
 30 minutes, "51", "52" and
 "53" alarm is indicated.
P18
  Insufficient/Excessive Voltage at Inverter
 Circuit or CB Connector Part
 When activating 3 times in
 30 minutes, "06" alarm is
 indicated.
P13
 ∆P = Pd - Ps
 - 
P16
 4-Way Valve
 Switching
 Control
 Discharge
 Gas
 SUPERHEAT
 Decrease
 Retry
 When activating 3 times in an
 hour, "45" alarm is indicated.
 When activating 2 times in
 2 hours (90min. For 24, 30HP),
 "07" alarm is indicated.
Protection Control
P07
P08
 Vacuum/Discharge Gas
 Temperature
 Increase Retry
 Pressure Ratio
 Control
 High-Pressure
 Increase Protection
 Current Protection
 Inverter Fin Temperature
 Increase Protection
 Discharge Gas
 Temperature Increase
 Protection
 Low-Pressure
 Decrease Protection
 Insufficient Voltage
  /Excessive Voltage
 Retry
 Oil Return
 Control
 Running Current Limit
 Control
 (For 24, 30HP)
 Pressure Ratio
 Decrease Retry
 Low-Pressure
 Increase Retry
 Overcurrent Retry of
 Constant Compressor
 High-Pressure
 Increase
 Retry
 High-Pressure
 Decrease Protection