Parameters accessible with Function Code 03, 06,10h
Custom map parameters
Revision 13 HC900 Process Controller Communications User Guide 97
April 2017
Parameter Name
Access
Notes
Event Month Grp-4 Evt-1
Thru
Event Month Grp-4 Evt-8
R/W
UNSIGNED 16 BIT
1 - 12
Event Month Grp-5 Evt-1
Thru
Event Month Grp-5 Evt-8
R/W
UNSIGNED 16 BIT
1 - 12
Event Day Grp-1 Evt-1
Thru
Event Day Grp-1 Evt-8
R/W
UNSIGNED 16 BIT
Day of month: 131
Day of week: 1 – 7 where 1 = Sunday
Event Day Grp-2 Evt-1
Thru
Event Day Grp-2 Evt-8
R/W
UNSIGNED 16 BIT
Day of month: 1 31
Day of week: 1 – 7 where 1 = Sunday
Event Day Grp-3 Evt-1
Thru
Event Day Grp-3 Evt-8
R/W
UNSIGNED 16 BIT
Day of month: 1 31
Day of week: 1 – 7 where 1 = Sunday
Event Day Grp-4 Evt-1
Thru
Event Day Grp-4 Evt-8
R/W
UNSIGNED 16 BIT
Day of month: 1 31
Day of week: 1 – 7 where 1 = Sunday
Event Day Grp-5 Evt-1
Thru
Event Day Grp-5 Evt-8
R/W
UNSIGNED 16 BIT
Day of month: 1 31
Day of week: 1 – 7 where 1 = Sunday
Special Day Mode
R/W
UNSIGNED 16 BIT
0 = disable outputs
1 = use alternate time
Special Day Out 1
Thru
Special Day Out 8
R/W
FLOAT 32 BIT
0 = normal behavior
1 = do what Special Day mode specifies
Special Day Day-1
Thru
Special Day Day-16
R/W
UNSIGNED 16 BIT
Day of month: 1 31
Day of week: 1 – 7 where 1 = Sunday