EasyManua.ls Logo

Honeywell HC900 - Fixed Map; Table 6-1 Fixed Map (Listed by Increasing Address)

Honeywell HC900
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters accessible with Function Code 03, 06,10h
Fixed Map
44 HC900 Process Controller Communications User Guide Revision 13
April 2017
6.2 Fixed Map
Table 6-1 describes the fixed register map for Function Code 03, 06 and 10h.
Except for User-Defined Signals and Variables, all items shown are assigned automatically to the
addresses shown.
Details on each item type are in sections 6.3 through 6.17.
There are several gaps of unused addresses in the fixed map; Table 6-1 does not explicitly show
these gaps, it shows only the range of addresses used by items. For example, there is a gap of
unused addresses between Loop 1’s end address 00FF and Loop 2’s start address 0140. There are
also gaps of unused addresses within Loop 1’s range.
Parameters for blocks such as Setpoint Programmers and Sequencers are divided into two or three
sections of the map.
Custom maps can contain additional quantities and parameters beyond what is included in the
fixed map.
Conversion between Address (Hex) Number and Register (Decimal) Number
To convert the address number to the register number, convert the address from hexidecimal to decimal and
add 1. Registers are addressed starting at zero: registers 1-16 are addressed as 0-15.
To convert the register number to the address number, subtract 1 from the register and convert to hex.
Table 6-1 Fixed Map (listed by increasing address)
Fixed
Start
Address
(hex)
Fixed
End
Address
(hex)
Item Description
See
section
0000
< 0040
Miscellaneous Parameters
6.3
0040
00FF
Loop #1 (floating point & bit packed)
6.4
0140
01FF
Loop #2 (floating point & bit packed)
0240
02FF
Loop #3 (floating point & bit packed)
0340
03FF
Loop #4 (floating point & bit packed)
0440
04FF
Loop #5 (floating point & bit packed)
0540
05FF
Loop #6 (floating point & bit packed)
0640
06FF
Loop #7 (floating point & bit packed)
0740
07FF
Loop #8 (floating point & bit packed)
0840
08FF
Loop #9 (floating point & bit packed)
0940
09FF
Loop #10 (floating point & bit packed)
0A40
0AFF
Loop #11 (floating point & bit packed)
0B40
0BFF
Loop #12 (floating point & bit packed)
0C40
0CFF
Loop #13 (floating point & bit packed)
0D40
0DFF
Loop #14 (floating point & bit packed)
0E40
0EFF
Loop #15 (floating point & bit packed)
0F40
0FFF
Loop #16 (floating point & bit packed)
1040
10FF
Loop #17 (floating point & bit packed)
1140
11FF
Loop #18 (floating point & bit packed)
1240
12FF
Loop #19 (floating point & bit packed)
1340
13FF
Loop #20 (floating point & bit packed)
1440
14FF
Loop #21 (floating point & bit packed)
1540
15FF
Loop #22 (floating point & bit packed)

Table of Contents

Other manuals for Honeywell HC900

Related product manuals