Parameters accessible with Function Code 03, 06,10h
Sequencer
Revision 13 HC900 Process Controller Communications User Guide 75
April 2017
Table 6-20 Sequencer 1-4 State Fixed Addresses
Starting
Address
(Hex)
Starting
Register
(Decimal)
Ending
Address
(Hex)
Ending
Address
(Decimal)
Sequencer #1 State Table
5CC0
23745
5CFF
23808
Sequencer #2 State Table
5F20
24353
5F5F
24416
Sequencer #3 State Table
6180
24961
61BF
25024
Sequencer #4 State Table
A220
41505
A25F
41568
Sequencer Parameters
Fixed addresses are for Sequencer #1. For fixed addresses of other Sequencers see Table 6-1, or Table
6-18, Table 6-19, and Table 6-20.
Parameters commonly used for controlling a sequencer are marked with a single asterisk*.
Parameters commonly used to define a sequence are marked with two asterisks **.
Note: in the custom map either all or none of the segment step data is addressed, you can’t specify which
steps get addressed.
The addresses given in Table 6-21 do not necessarily apply to sequencers in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-21 Sequencer Parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter
Access
Notes
5AA0
23201
Not used
N/A
Not used
5AA1
23202
Save current sequence
request**
R/W
Integer, Saves current sequence to
archive and assigns it to the number
written (1-20).
5AA2
23203
Reset*
W
Integer, Write to this location results in
reset action and data is ignored.
5AA3
23204
Run*
W
Integer, Write to this location starts run
action and data is ignored.
5AA4
23205
Hold*
W
Integer, Write to this location results in
reset action and data is ignored.
5AA5
23206
Advance*
W
Integer, Write to this location results in
an advance to next step and data is
ignored.
Writing to this register is only permissible
in the hold mode.
5AA6
23207
Not used
N/A
Not used
5AA7
23208
Step jumped to on Jog*
R/W
Integer Step number for jog.
5AA8
23209
Current Sequence number *
R
Integer Sequence number loaded.
5AA9
23210
Step Number*
R
Integer value for current step number.
5AAA
23211
Load Sequence number *
R/W
Integer, sequence number loaded to
sequencer. Writing to this register is only
permissible in the Ready mode.