Parameters accessible with Function Code 03, 06,10h 
Sequencer 
76  HC900 Process Controller Communications User Guide  Revision 13 
    April 2017 
Step number change request* 
Integer, go to a step number in any 
mode. 
Integer, Bit packed for 16 output values 
0:OFF 1:ON 
Integer, 0=hrs, 1=minutes. 
Floating point value for elapsed 
sequence time in minutes. 
Time Remaining in current step* 
Floating point value for time remaining in 
current step in minutes. 
Integer value for bit packed current 
sequence state : 
Bit 0 = Ready 
Bit 1 = Run 
Bit 2 =Hold 
Bit 3 = Stop 
Bit 4 = Disable 
Bit 5 = time units (minutes) 
Bit 6 = time units (hours) 
Integer value for current state number 
Floating point value auxiliary output 
The following parameters are partitioned as Sequencer Steps and are not contiguous with the previous partition. 
All 64 steps are used to define a sequence. 
Sequencer #1 Step #1 Time 
Next step 
Integer value of the next step executed 
when time expires. 
Sequencer #1 Step #1 Event1 
Next step 
Integer value of the next step executed 
when configured event 1 transitions from 
OFF to ON. 
Sequencer #1 Step #1 Event2 
Next step 
Integer value of the next step executed 
when configured event 2 transitions from 
OFF to ON. 
Sequencer #1 Step #1 Advance 
Next step 
Integer value of the next step executed 
when Advance transitions from OFF to 
ON. 
Sequencer #1 Step #1 Step 
Time 
Floating value for time of present step. 
Sequencer #1 Step #1 Auxiliary 
Output 
Floating Auxiliary analog value 
associated with the step. 
Sequencer #1 Step #2 Time 
Next step 
Integer value of the next step executed 
when time expires. 
Sequencer #1 Step #64 
Auxiliary Output 
Floating Auxiliary analog value 
associated with the step. 
The following parameters are partitioned as Sequencer States and are contiguous with the previous partition. All 
64 state numbers are used to define a sequence.