EasyManua.ls Logo

Honeywell HC900 - 3 Modbus Double Register Format; Table 3-1 Modbus Double Register Format Selections

Honeywell HC900
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus Double Register Format
IEEE Floating Point Data Format
10 HC900 Process Controller Communications User Guide Revision 13
April 2017
3. Modbus Double Register Format
Data that is 32 bits requires 2 sequential registers (4 bytes) to transfer its data. Data of this type includes IEEE 32-bit
floating point, 32-bit signed integer and 32-bit unsigned integer. The stuffing order of the bytes into the two registers
differs among Modbus/TCP hosts. To provide compatibility, the double register format for the HC900 controller is
configurable.
To set the controller’s double register byte order, go to the “Set Controller Network Parameters ” wizard in the
"Controller Utilities Function" section of the Utilities Tab on the Process Control Designer and configure “Modbus
Double Register Format”. This can be done in the RUN mode.
The selections are:
Table 3-1 Modbus Double Register Format Selections
Selection
Description
Byte order
(See Figure 2-1)
Notes
FP B
Floating Point Big Endian Format
4, 3, 2, 1
HC900 default
FP BB
Floating Point Big Endian with
byte-swapped
3, 4, 1, 2
FP L
Floating Point Little Endian Format
1, 2, 3, 4
FP LB
Floating Point Little Endian with
byte-swapped
2, 1, 4, 3
Modicon and
Wonderware
standard
See IEEE Formats on page IEEE Floating Point Formats on page 11 and 32-bit integer formats on page 13.
NOTE: Byte Swapping only applies to Function Codes 3, 4, and 16.

Table of Contents

Other manuals for Honeywell HC900

Related product manuals