Parameters accessible with Function Code 03, 06,10h 
Ramp 
Revision 13  HC900 Process Controller Communications User Guide  81 
April 2017 
6.13 Ramp 
Summary 
This section contains parameters and addresses for the Ramp.   
See the Ramp Register Maps in Table 6-1 for starting and ending addresses (hex) for Ramp #2 through 
Ramp #8 Map Addresses. 
The Modbus Ramp number address for a Ramp can also be obtained from the Process Control Designer printout 
of "Block Modbus Addresses".  
Function Code Support: 
Reads – Function Code 3 
Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point) 
Writes – Function Code 6 for presetting an integer value 
For custom addresses view or print a report in HC Designer. 
Table 6-23 Ramp Parameters  
Floating Point in Engineering Units 
Floating Point in Engineering Units 
Floating Point in Engineering Units 
Floating Point in Seconds 
Floating Point in Engineering Unit/Second 
Floating Point in Engineering Unit/Second 
Bit 0: Ramp #1 Enable: 0=NO, 1=YES 
Bit 1: Ramp #2 Enable: 0=NO, 1=YES 
Bit 2: Ramp #3 Enable: 0=NO, 1=YES 
Bit 3: Ramp #4 Enable: 0=NO, 1=YES 
Bit 4-15: Unused 
Ramp #1-4 Override 
Status 
Bit 0: Ramp #1 Override Active: 0= NO, 1=YES 
Bit 1: Ramp #1 Override to High Limit:  
 0=Low Limit, 1= High Limit  
Bit 2: Ramp #2 Override Active: 0= NO, 1=YES  
Bit 3: Ramp #2 Override to High Limit: 
 0=Low Limit, 1= High Limit 
Bit 4: Ramp #3 Override Active: 0= NO, 1=YES 
Bit 5: Ramp #3 Override to High Limit:  
 0=Low Limit, 1= High Limit 
Bit 6: Ramp #4 Override Active: 0= NO, 1=YES 
Bit 7: Ramp #4 Override to High Limit:  
 0=Low Limit, 1= High Limit 
Bit 8-15: Unused 
Ramp #1 Output 
Scale High 
Floating Point in Engineering Units