Parameters accessible with Function Code 03, 06,10h
Ramp
82 HC900 Process Controller Communications User Guide Revision 13
April 2017
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name
Access
Notes
6410
25617
Ramp #2 Output
Scale High
R/W
Floating Point in Engineering Units
6412
25619
Ramp #3 Output
Scale High
R/W
Floating Point in Engineering Units
6414
25621
Ramp #4 Output
Scale High
R/W
Floating Point in Engineering Units
6416
25623
Ramp #1 Output
Scale Low
R/W
Floating Point in Engineering Units
6418
25625
Ramp #2 Output
Scale Low
R/W
Floating Point in Engineering Units
641A
25627
Ramp #3 Output
Scale Low
R/W
Floating Point in Engineering Units
641C
25629
Ramp #4 Output
Scale Low
R/W
Floating Point in Engineering Units
641E
25631
Ramp #1 Input Limit
High
R/W
Floating Point in Engineering Units
6420
25633
Ramp #2 Input Limit
High
R/W
Floating Point in Engineering Units
6422
25635
Ramp #3 Input Limit
High
R/W
Floating Point in Engineering Units
6424
25637
Ramp #4 Input Limit
High
R/W
Floating Point in Engineering Units
6426
25639
Ramp #1 Input Limit
Low
R/W
Floating Point in Engineering Units
6428
25641
Ramp #2Input Limit
Low
R/W
Floating Point in Engineering Units
642A
25643
Ramp #3Input Limit
Low
R/W
Floating Point in Engineering Units
642C
25645
Ramp #4Input Limit
Low
R/W
Floating Point in Engineering Units