Parameters accessible with Function Code 03, 06,10h
Scheduler
Revision 13 HC900 Process Controller Communications User Guide 71
April 2017
Segment registers
The table below describes the registers that are part of a setpoint schedule. A schedule contains 50
segments. Each segment is made up of 28 parameters (Segment n Guaranteed Soak Type 1 through
Segment n Recycle Segment) which consumes 48 (30 hex) registers, for a total of 2400 contiguous
registers. This table contains fixed addresses of Schedule #1 Segments; see Table 6-1 for fixed addresses of
Schedule Segments. In a custom map the segment registers contiguously follow the other Schedule registers
listed in Table 6-15.
All 50 segments are used to define a schedule. You can’t specify which segments get assigned.
The addresses given in Table 6-17 do not necessarily apply to segments in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-17 Schedule Segments 1-50
Fixed
Start
Address
(Hex)
Fixed
Start
Register
(Decimal)
Segment #1 Guaranteed Soak
Type 1
(Bit Packed)
Bit 0: Off
Bit 1: Low
Bit 2: High
Bit 3: Low & High
Bit 4…15: Unused
Note 1
Segment #1 Guaranteed Soak
Type 2
See Guaranteed Soak Type 1
Segment #1 Guaranteed Soak
Type 3
See Guaranteed Soak Type 1
Segment #1 Guaranteed Soak
Type 4
See Guaranteed Soak Type 1
Segment #1 Guaranteed Soak
Type 5
See Guaranteed Soak Type 1
Segment #1 Guaranteed Soak
Type 6
See Guaranteed Soak Type 1
Segment #1 Guaranteed Soak
Type 7
See Guaranteed Soak Type 1
Segment #1 Guaranteed Soak
Type 8
See Guaranteed Soak Type 1
Bit 0: Event #1
: :
Bit 15: Event #15
0: Event OFF
1: Event ON
Note 2
Floating Point in seconds Note
1
Segment #1 Output #1 Ramp or
Soak value
Segment #1 Output #2 Ramp or
Soak value
Segment #1 Output #3 Ramp or
Soak value
Segment #1 Output #4 Ramp or
Soak value