Parameters accessible with Function Code 03, 06,10h
Scheduler
Revision 13 HC900 Process Controller Communications User Guide 71
April 2017
Segment registers
The table below describes the registers that are part of a setpoint schedule. A schedule contains 50
segments. Each segment is made up of 28 parameters (Segment n Guaranteed Soak Type 1 through
Segment n Recycle Segment) which consumes 48 (30 hex) registers, for a total of 2400 contiguous
registers. This table contains fixed addresses of Schedule #1 Segments; see Table 6-1 for fixed addresses of
Schedule Segments. In a custom map the segment registers contiguously follow the other Schedule registers
listed in Table 6-15.
All 50 segments are used to define a schedule. You can’t specify which segments get assigned.
The addresses given in Table 6-17 do not necessarily apply to segments in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-17 Schedule Segments 1-50
Fixed
Start
Address
(Hex)
Fixed
Start
Register
(Decimal)
Offset
(Hex)
Offset
(Decimal)
Parameter Name
Access
Notes
3200
12801
0000
0000
Segment #1 Guaranteed Soak
Type 1
(Bit Packed)
R/W
Bit Packed
Bit 0: Off
Bit 1: Low
Bit 2: High
Bit 3: Low & High
Bit 4…15: Unused
Note 1
3201
12802
0001
0001
Segment #1 Guaranteed Soak
Type 2
R/W
See Guaranteed Soak Type 1
3202
12803
0002
0002
Segment #1 Guaranteed Soak
Type 3
R/W
See Guaranteed Soak Type 1
3203
12804
0003
0003
Segment #1 Guaranteed Soak
Type 4
R/W
See Guaranteed Soak Type 1
3204
12805
0004
0004
Segment #1 Guaranteed Soak
Type 5
R/W
See Guaranteed Soak Type 1
3205
12806
0005
0005
Segment #1 Guaranteed Soak
Type 6
R/W
See Guaranteed Soak Type 1
3206
12807
0006
0006
Segment #1 Guaranteed Soak
Type 7
R/W
See Guaranteed Soak Type 1
3207
12808
0007
0007
Segment #1 Guaranteed Soak
Type 8
R/W
See Guaranteed Soak Type 1
3208
12809
0008
0008
Segment #1 Events
R/W
Bit Packed
Bit 0: Event #1
: :
Bit 15: Event #15
0: Event OFF
1: Event ON
Note 2
320A
12811
000A
0010
Segment #1 Time
R/W
Floating Point in seconds Note
1
320C
12813
000C
0012
Segment #1 Output #1 Ramp or
Soak value
R/W
Floating Point Note 1
320E
12815
000E
0014
Segment #1 Output #2 Ramp or
Soak value
R/W
Floating Point Note 1
3210
12817
0010
0016
Segment #1 Output #3 Ramp or
Soak value
R/W
Floating Point Note 1
3212
12819
0012
0018
Segment #1 Output #4 Ramp or
Soak value
R/W
Floating Point Note 1