Modbus Double Register Format
IEEE Floating Point Formats
Revision 13 HC900 Process Controller Communications User Guide 11
April 2017
3.1 IEEE Floating Point Formats
S E7 E6 E5 E4 E3 E2 E1
E0 M22 M21M20 M19 M18 M17 M16
REGISTER N
(High)
REGISTER N+1
(Low)
M15 M14 M13 M12 M11 M10 M9 M8
M7 M6 M5 M4 M3 M2 M1 M0
High Low High Low
Bit 0
Bit 31
FP B - Floating Point Big Endian Format:
S=Sign E=Exponent M=Mantissa
S E7 E6 E5 E4 E3 E2 E1
E0 M22 M21M20 M19 M18 M17 M16
REGISTER N
(High)
REGISTER N+1
(Low)
M15 M14 M13 M12 M11 M10 M9 M8
M7 M6 M5 M4 M3 M2 M1 M0
High Low High Low
Bit 8
FP BB - Floating Point Big Endian with Byte Swapped Format:
S=Sign E=Exponent M=Mantissa
Bit 31
Bit 24
Bit 23
Bit 16
Bit 7
Bit 0
Bit 15