Parameters accessible with Function Code 03, 06,10h
Scheduler
70 HC900 Process Controller Communications User Guide Revision 13
April 2017
Bit 0: 1=Ready
1: 1=Run
2: 1=Hold
3: 1=End
4: 1=Time Units in Seconds
5: 1=Time Units in Minutes
6: 1=Time Units in Hours
7: If bit 2 Set
0: Operator hold
1: Guaranteed soak hold
8-15: Reserved
Write to location Starts Schedule;
Data ignored
Write to location Holds Schedule;
Data ignored
Write to location Advances Schedule;
Data ignored
Write to location Resets Schedule;
Data ignored
Bit 0: Reserved 1: minutes
2: hours
3-15: Unused
Scheduler Segment Fixed Register Map
A schedule can contain up to 50 segments. Each segment is made up of 48 (30 hex) registers, for a total of
2400 contiguous registers. This table contains Segment Map fixed addresses of SP Scheduler #1. See Table
6-1 for starting and ending addresses (hex) for SP Scheduler #2 Addresses.
The addresses given in Table 6-16 do not necessarily apply to scheduler segments in the custom map. For
custom addresses view or print a report in HC Designer.
Table 6-16 Scheduler #1 Segment Fixed Addresses
Fixed
Start
Address
(Hex)
Fixed
Start
Register
(Decimal)
Fixed End
Register
(Decimal)