Parameters accessible with Function Code 03, 06,10h
Device Control
90 HC900 Process Controller Communications User Guide Revision 13
April 2017
6.16 Device Control
Summary
This table contains addresses for the Device Control group #1.
See the Device Control Register Maps in Table 6-1 for starting and ending addresses (hex) for Device
Control #2 through Device Control #16 Map Addresses.
The Modbus Device Control number address for a Device Control can also be obtained from the Process
Control Designer report.
Function Code Support:
Reads – Function Code 3
Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point )
Writes – Function Code 6 for presetting an integer value
For custom addresses view or print a report in HC Designer.
Table 6-26 Device Control parameters
Bits 0 – 6: Device Control State
Bit 0: Ready: 0=NO, 1=YES
Bit 1: Prestart: 0=NO, 1=YES
Bit 2: Starting: 0=NO, 1=YES
Bit 3: Running: 0=NO, 1=YES
Bit 4: Stopping: 0=NO, 1=YES
Bit 5: Disabled: 0=NO, 1=YES
Bit 6: Failed: 0=NO, 1=YES
Bit 7: Run Request Input State; 0=OFF, 1=ON
Bit 8: Device Feedback Started; 0=NO, 1=YES
Bit 9: Device Failed; 0=NO, 1=YES
Bit 10: Automatic Reset; 0=Manual, 1=Auto
Bit 11-15: Unused
Floating Point in Seconds
Floating Point in Seconds
Floating Point in Seconds
Floating Point in Seconds