Parameters accessible with Function Code 03, 06,10h
Set Point Programmer
Revision 13 HC900 Process Controller Communications User Guide 61
April 2017
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter
Access
Notes
1F10
7953
Jog Segment
R/W
Floating Point
Writing to this register is only permissible in
the reset or ready mode
1F12
7955
Loop Start
R/W
Floating Point
0 indicates no loop.
Writing to this register is only permissible in
the reset or ready mode
1F14
7957
Loop End
R/W
Floating Point
0 indicates no loop.
Writing to this register is only permissible in
the reset or ready mode
1F16
7959
Repeats
R/W
Floating Point
0 indicates loop forever.
Writing to this register is only permissible in
the reset or ready mode
1F3A
7995
Time Units**
R/W
Bit Packed
Bit 0: Reserved
1: minutes
2: hours
3-15: Unused
1F3B
7996
Ramp Units**
R/W
Bit Packed
Bit 0: 0:Time; 1:Rate
Bit 1-15: Unused
Writing to this register is only permissible in
the reset or ready mode
1F3C
7997
Guaranteed Soak Type **
R/W
Bit Packed
For selection of Soak (or Hold) guarantee
Per Segment (requiring selection per
segment in a table)
Bit 0: per segment
1: all soaks
2: all segments
3-15: Unused
None if none of the bits is set
Writing to this register is only permissible in
the reset or ready mode