Parameters accessible with Function Code 03, 06,10h
Stage
Revision 13 HC900 Process Controller Communications User Guide 79
April 2017
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name
Access
Notes
6206
25095
Stage #1-4
Previous/Next
Interlock
R
Bit Packed:
Bit 0: Stage #1 Interlock with Previous Stage
0=NO, 1=YES
Bit 1: Stage #1 Interlock with Next Stage
0=NO, 1=YES
Bit 2: Stage #1 Error with Interlocks
0=NO, 1=YES
Bit 3: Stage #2 Interlock with Previous Stage
0=NO, 1=YES
Bit 4: Stage #2 Interlock with Next Stage
0=NO, 1=YES
Bit 5: Stage #2 Error with Interlocks
0=NO, 1=YES
Bit 6: Stage #3 Interlock with Previous Stage
0=NO, 1=YES
Bit 7: Stage #3 Interlock with Next Stage
0=NO, 1=YES
Bit 8: Stage #3 Error with Interlocks
0=NO, 1=YES
Bit 9: Stage #4 Interlock with Previous Stage
0=NO, 1=YES
Bit 10: Stage #4 Interlock with Next Stage
0=NO, 1=YES
Bit 11: Stage #4 Error with Interlocks
0=NO, 1=YES
Bit 12 - 15: Unused
6207
25096
Stage #1-4 Output
Status (Request)
R
Bit Packed:
Bit 0: Stage #1 Output Enable: 0=NO, 1=YES
Bit 1: Stage #1 Output ON: 0=OFF, 1=ON
Bit 2: Stage #2 Output Enable: 0=NO, 1=YES
Bit 3: Stage #2 Output ON: 0=OFF, 1=ON
Bit 4: Stage #3 Output Enable: 0=NO, 1=YES
Bit 5: Stage #3 Output ON: 0=OFF, 1=ON
Bit 6: Stage #4 Output Enable: 0=NO, 1=YES
Bit 7: Stage #4 Output ON: 0=OFF, 1=ON
Bit 8-15: Unused
6208
25097
Stage #1 ON
Setpoint
R/W
Floating Point in Engineering Units
620A
25099
Stage #2 ON
Setpoint
R/W
Floating Point in Engineering Units
620C
25101
Stage #3 ON
Setpoint
R/W
Floating Point in Engineering Units