12 FireWarden 100-2/E — P/N 52778:A 11/04/2005
Product Description Specifications
Communication Confirmation (Kissoff) LED
Touchtone/Rotary dialing
Programmable Make/Break Ratio
EIA-232 Printer/PC interface (variable baud rate)
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 1,000 event capacity
Advanced fire technology features:
Automatic drift compensation
Maintenance alert
Detector sensitivity test capability (NFPA 72 compliant)
Automatic device type-code verification
Point trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with
two-stage capability
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, AFM
annunciators or FDU-80 Remote annunciator
Auto-program (learn mode) reduces installation time. Reports two devices set to the same
address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or optional keyboard
Upload/Download (local or remote) of program and data via integral DACT
Compatible with FireWarden’s addressable devices (refer to the FireWarden SLC Wiring
Manual for a list of compatible addressable devices)
Optional 4XTM module (conventional reverse polarity/city box transmitter)
Annunciators:
ACS Series-LED Zone Annunciators
LDM Graphic Annunciator Series
FDU-80 Liquid Crystal Display point annunciator
ACM-8R Relay Module
1.2 Specifications
Refer to Figure 1.1 on page 9 for terminal locations and connections.
AC Power - TB11
NFW2-100: 120 VAC, 60 Hz, 3.0 amps
NFW2-100E: 240 VAC, 50 Hz, 1.5 amps
Wire size: minimum 14 AWG (2.00 mm
2
) with 600 V insulation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER FireWarden-100-2 and is the answer not in the manual?

Honeywell NOTIFIER FireWarden-100-2 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER FireWarden-100-2
CategoryFire Alarms
LanguageEnglish

Related product manuals