FireWarden 100-2/E — P/N 52778:A 11/04/2005   21
Telephone Requirements and Warnings Product Description
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone 
line.  Excessive RENs on the telephone line may result in the devices not ringing in response to an 
incoming call.  In most, but not all areas, the sum of the RENs should not exceed five (5.0).  To be 
certain of the number of devices that may be connected to the line as determined by the total RENs, 
contact the telephone company to determine the maximum REN for the calling area.
1.10.2  Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of 
two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty 
information, please contact: 
Manufacturer: Notifier
12 Clintonville Road
Northford, CT 06472
(203) 484-7161
Product Model Number: FireWarden-100-2
FCC Registration Number: US:1W6AL00B9200UD
Ringer Equivalence: 0.0B
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency 
situation.  It must be able to do this even if other equipment (telephone, answering system, 
computer modem, etc.) already has the telephone line in use.  To do so, alarm dialing equipment 
must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of 
all other equipment attached to the same telephone line.  If there are any questions concerning these 
instructions, consult the telephone company or a qualified installer about installing the RJ31X jack 
and alarm dialing equipment.   Refer to “Digital Communicator” on page 33 for an illustration of 
the proper installation of this equipment.
Important!  The DACT must not 
be used to dial a phone number that is call-forwarded per 
requirements of UL 864 9th Edition.
1.10.3  Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or 
make changes in its facilities, services, equipment or procedures which may affect the operation of 
this control panel.  However, the telephone company is required to give advance notice of such 
changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right 
to temporarily discontinue service.  Advance notification will be provided except in cases when 
advance notice is not practical.  In such cases, notification will be provided as soon as possible.  
The opportunity will be given to correct any problems and to file a complaint with the FCC if you 
believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY 
LINE SERVICES.
NOTE: This equipment complies with Part 68 of the FCC rules and the requirements adopted by 
the ACTA.  On the inside of the FACP door is a label that contains, among other information, a 
product identifier in the format US:AAAEQ##TXXXX.  If requested, this number must be provided 
to the telephone company.