FireWarden 100-2/E — P/N 52778:A 11/04/2005   133
Special System Timers Operating Instructions
When a detector triggers an alarm, the onboard piezo sounds immediately, but the NACs are 
prevented from activating for 15 seconds.  This inhibit time is factory set and cannot be changed.  
Pressing the Alarm Silence or Acknowledge/Step key during the 15 second inhibit time will silence 
the piezo sounder and start a timer which prevents activation of NACs for an additional time 
duration which can be user programmed for up to three minutes.  After the programmed delay, the 
NACs will activate if the source of the alarm is not cleared.  Note that if a second alarm occurs 
during either time delay, the alarm will be processed immediately, causing activation of the 
appropriate output zones.  The events which occur upon PAS activation are as follows:
• onboard piezo sounds immediately
• control panel LCD display will indicate a presignal event and the active point
• control points programmed to Zone 97 will activate
• annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone LED
• outputs (NACs and control modules) of associated zones will be inhibited from activating 
for a factory set duration of 15 seconds
• pressing the Alarm Silence or Acknowledge/Step key will start a timer which inhibits output 
activation for additional time delay of up to three minutes which is user programmable
• second alarm occurring anytime during either time delay will cause immediate activation of 
all associated outputs
PAS operation requires the approval of the local Authority Having Jurisdiction.
Note that the PAS BYPASS monitor type code, when activated, will inhibit the PAS capability until 
the PAS BYPASS monitor is deactivated.  While PAS is inhibited, signaling devices will 
immediately place the control panel into alarm.  This feature may be employed by wiring a 
normally open device, such as a switch, to a monitor module which has been  programmed for PA S  
BYPASS.
4.20  Special System Timers
4.20.1  Silence Inhibit Timer
This option, if selected, prevents the Alarm Silence key from functioning for 60 seconds following 
an alarm.  A new alarm during the initial 60 second period will not
 cause the timer to restart with a 
new 60 seconds.  Silence Inhibit operation requires the approval of the local Authority Having 
Jurisdiction.
4.20.2  Autosilence Timer
If Autosilence is selected, the notification appliances, programmed as silenceable, will 
automatically be silenced after a programmable duration of from 5 to 30 minutes.  Pressing the 
Drill key will restart the timer.  Autosilence operation requires the approval of the local Authority 
Having Jurisdiction.
4.20.3  Trouble Reminder
If selected, this feature causes a reminding ‘beep’ every 15 seconds during an alarm (after the 
Alarm Silence key is pressed) and every two minutes during a trouble condition (after the 
Acknowledge/Step or Alarm Silence key is pressed).  The ‘beeps’ from the onboard piezo sounder 
will occur until the alarm or fault is cleared.
Note that if the trouble is not cleared within 24 hours, the piezo will resound, indicating that the 
trouble condition still exists.