FireWarden 100-2/E — P/N 52778:A 11/04/2005   37
Optional Module Installation Installation
Note that the printer may or may not be supervised as determined by user programming.  Refer 
to“Printer/PC” on page 112.
Printer Configuration
Refer to the documentation supplied with the printer for pertinent information about printer setup.  
Set the printer’s options as listed in the following table: 
PC Configuration
The Windows-based VeriFire Warden Programming Utility Kit contains CD-ROM with on-line 
help file.
2.9.3  Digital Communicator and Annunciators
ACM-8R Relay Control Module
The ACM-8R module provides eight Form-C relays with contacts rated for 5 amps.  When installed 
with an NFW2-100 FACP, the ACM-8R modules provide relay activation for each of the 99 
possible FACP zones plus special functions.  Options exist to allow for alarm only or alarm and 
trouble activation per zone.  Output activation for general alarm, general trouble, general 
supervisory, NAC fault, AC fail, walktest start and battery trouble are also available.  The ACM-8R 
can be mounted remotely in an ABS-8R annunciator surface-mount backbox.  Refer to the 
ACM-8R manual for information on setting module switches for addressing and relay functions.
ACS and AFM Series Annunciators
ACS and AFM Series Annunciators provide visual indications of FACP status in remote locations.  
Refer to the appropriate annunciator manual for information on installation, wiring and operation.  
COMMUNICATION SETUP
BUFFER: LARGE
DATA BITS: 7
PARITY: EVEN
STOP BIT: 1 STOP
BAUD RATE: 2400/4800/9600
AUTOMATIC LINE FEED NO
AUTOMATIC CARRIAGE RETURN NO
Table 2.1  Printer Options
Black
RCV
DTR
GRND
TX
5   4 3   2   1
9   8   7   6
White
Green
Red
B+   A+  B-   A-    A    B
ACS
SHIELDSLCSLC
SLC
SLC
OUT+ IN+ OUT- IN-
TB8 TB9 TB10
PRT/PK-CABLE
9600tb7a.cdr
Figure 2.17  Serial Printer and Computer Connections