38 FireWarden 100-2/E — P/N 52778:A 11/04/2005
Installation Optional Module Installation
Annunciator addressing is specific to the NFW2-100 control panel. The following table describes
the annunciator addresses and the corresponding addressable devices that will be annunciated at
each annunciator address.
The NFW2-100 must be programmed for the annunciators installed on the system. Refer to
“Annunciators/UDACT” on page 93 for information on annunciator programming. Make certain
to program the annunciator addresses that have been physically installed on the system.
Note: The 8 General System Status Points include the following:
ACM Annunciator Address Annunciator Displays the Following Points
1 8 General System Status Points & Zones 1 - 56
2 Zones 57 - 99 & 4 NACs
3 SLC Loop, Module Addresses 1 - 64
4 not used
5 SLC Loop, Module Addresses 65 - 99
6 not used
7 not used
8 SLC Loop, Detector Addresses 1 - 64
9 not used
10 SLC Loop, Detector Addresses 65 - 99
11 not used
12 not used
13 not used
14 not used
15 not used
16 not used
17 not used
18 not used
19 not used
20 8 General System Status Points & Zones 1 - 56
21 Zones 57 - 99 & 4 NACs
22 SLC Loop, Module Addresses 1 - 64
23 not used
24 SLC Loop, Module Addresses 65 - 99
25 not used
26 not used
27 SLC Loop, Detector Addresses 1 - 64
28 not used
29 SLC Loop, Detector Addresses 65 - 99
30 not used
31 not used
32 not used
Table 2.1 ANnunciator Address Displays
• • General Alarm • • Alarm Silenced • • Battery Fault
• • General Trouble • • System Off Normal • • NAC Fault
• • General Supervisory • • AC Loss